The ACB E1.2N is a 4P circuit breaker with a rated current (In) of 1250A. It has an Icu rating of 66kA at 415V AC, indicating its ability to interrupt short-circuit currents. The circuit breaker also has a rated short-time withstand current, Icw (1s), of 50kA.
The ACB E1.2N features a withdrawable auto EKIP touch LSIG trip unit, which provides protection against overloads, short circuits, and ground faults. It is equipped with a shunt closing mechanism that operates on either 24VAC or 24VDC power supply.
This complete package includes the WMP+FP+YC components necessary for proper operation.