The ACB E1.2N is a 4P circuit breaker with a rated current (In) of 800A. It has an Icu rating of 66kA at 415V AC, indicating its ability to interrupt short-circuit currents. The breaker also has a rated short-time withstand current, Icw (1s), of 50kA.
It features a withdrawable auto EKIP touch LSIG trip unit, which provides protection against overload, short circuit, and ground fault conditions. Additionally, the ACB E1.2N includes a motor operator that operates on 110-120VAC/DC power.
This complete package includes the WMP+FP+MOP components necessary for proper operation.