Products

ABB E2N320WO250K ACB W/Fixed Part 800-2000A 3-P 66kA 240-250VAC/DC Shunt Opening E2.2 Ekip Touch LSIG

Product Code: E2N320WO250K

  • Automatic ACB for efficient protection
  • Rated current range: 800-2000 A
  • High breaking capacity of 66 kA
  • Ekip Touch LSIG trip unit included
  • Complies with IEC 309 standards
In Stock Low Stock Out Of Stock Please See Attributes

Specifications

Size of Frame E2.2
G (0.1 to 1 x In) - I4 (A) 200-2000
I (1.5 to 15 x In) - I3 (A) 3000-30000
L (0.4 to 1 x In) - I1 (A) 800-2000
No. of Poles 3P
Power Loss (W) 450
Rated Current (A) 2000
Rated Impulse Withstand Voltage (kV) 12
Rated Insulation Voltage AC (V) 1000
Rated Operational Voltage AC (V) 690
Rated Short-time Withstand Current - Icw (kA/1s) 66
Rated Uninterrupted Current - Iu (A) 2000
S (0.6 to 10 x In) - I2 (A) 1200-20000
Breaking Capacity 415V AC - Icu (kA) 66
Poles 3P
Breaking Capacity (kA) 66 @415V AC
Current Rating (A) 2000
Trip Unit - Electronic EKIP Touch LSIG
AC Voltage (V) 690
Frame E2.2
Icw (kA/1s) - Short-time Withstand Current Rating 66
Iu - Uninterrupted Current Rating (A) 2000
Product Type Circuit Breaker
Brand ABB
Breaking Capacity 66 kA
Component Type Withdrawable
Frame Size E2.2
Number of Poles 3
Power Loss 450 W
Rated Current 800-2000 A
Rated Impulse Withstand Voltage 12 kV
Rated Insulation Voltage 1000 VAC
Rated Short Time Withstand Current 66 kA
Rated Voltage 690 VAC
Standards and Approvals IEC 309
Terminal Type Horizontal Rear Spread
Trip Unit Ekip Touch LSIG
Version Withdrawable

Description

The Automatic ACB (Air Circuit Breaker) you're considering is a reliable choice for industrial and commercial applications, offering robust performance across various electrical systems. Designed to handle demanding conditions, this ACB supports a rated current range of 800 to 2000 A, making it adaptable for different load requirements. One of the standout features is its Rated Impulse Withstand Voltage of 12 kV and Rated Insulation Voltage of 1000 VAC. These specifications ensure that the circuit breaker can withstand high-voltage transients and maintain insulation integrity under normal operating conditions. Moreover, with a Rated Short Time Withstand Current and Breaking Capacity both at an impressive 66 kA, this product provides excellent protection against short circuits by ensuring any faults are swiftly managed to prevent damage to your system. Operating at a Rated Voltage of 690 VAC, the unit integrates seamlessly into standard power distribution networks. The Ekip Touch LSIG trip unit offers advanced protection functions including Long-time, Short-time, Instantaneous, and Ground fault protections—ensuring comprehensive safety measures are in place. This model features a Frame Size of E2.2 and comes with Horizontal Rear Spread terminals which facilitate convenient installation in varied configurations. It's designed with three poles providing adequate separation for each phase in multi-phase systems. The power loss is rated at 450 W—a crucial factor when considering energy efficiency and thermal management within your setup. Compliance with IEC 309 standards underscores its reliability and adherence to international quality benchmarks. In summary, this Automatic ACB combines durability with precision engineering suited for rigorous environments where reliability cannot be compromised. It’s an ideal fit if you’re seeking dependable circuit protection tailored for substantial electrical loads while maintaining compliance with global standards.