Product Code: 1SDA067648R1

C.BREAKER TMAX XT2L 160 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMA R 160 I3=800...1600 A

Technical Specifications

Brand ABB
EAN 8015644015442
Breaking Capacity 415V AC - Icu (kA) 120
Current Rating (A) 160
Design of Control Element Toggle
Main Circuit Electrical Connection Bolt Connection
Main Current Circuit Connection Position Front Side
No. of Poles 3
Overload Release Current Setting (A) 112
Power Loss (W) 16.15
Rated Current (A) 160
Rated Instantaneous Short-Circuit Current - Ii (A) 800
Rated Uninterrupted Current - Iu (A) 160
Rated Voltage (V) 690
Size of Frame XT2
Trip Unit TMA
Degree of Protection IP20
MCCB Type XT2 Frame
Poles 3P
Breaking Capacity (kA) 120
Tripping Unit TMA
Trip Unit - Thermal Magnetic TMA

Documents

Products to compare:
Comparing Products