AC 380-480V Wide-range input. Input fuses included. Requires only two legs of a 3-phase system. Width only 40mm. Efficiency up to 85.8%. Input-transient blanking circuit included. Minimal inrush current surge. Full power between -25°C and +60°C. --- Introducing our AC power supply with a wide-range input of 380-480V. This compact device is designed to fit into tight spaces with its width of only 40mm. It includes input fuses for added protection and requires only two legs of a 3-phase system, making installation easier. With an efficiency rating of up to 85.8%, this power supply ensures optimal performance while minimizing energy waste. The inclusion of an input-transient blanking circuit helps to suppress anyVoltage spikes or fluctuations, providing stable and reliable power output. One notable feature of this power supply is its minimal inrush current surge, which prevents excessive current flow during startup, reducing stress on the electrical system. Operating within a wide temperature range from -25°C to +60°C, this power supply delivers full power even in extreme conditions. Choose our AC power supply for efficient and reliable performance in your electrical systems.

Technical Specifications

Brand PULS
AC Input Type Wide-range
Conformal Coating No
Connection Type Screw terminals
Country of Origin China / Czech Republic
Customs Tariff Number 85044083
Degree of Protection IP20
Derating 2.5 W/°C
Derating Temperature (°C) > +60
Dimensions (mm) 40W x 124H x 117D
E Classification E-CS01
Efficiency 85.40%
External Input Fuse Recommendation B-6 A / C-3 A
Family DIMENSION
Harmonic Correction PFC
Input Inrush Current (A) 4 / 4
Input Inrush Current Limitation Active
Input Voltage Range AC (V) 380-480
Integrated Decoupling Function No
Maximum Ripple and Noise Voltage (mVpp) 100
Mounting Type DIN Rail
Operational Temperature Range (°C) -25 to 70
Output Current Range (A) 8 - 6.4
Output Power (W) 96
Output Voltage (V) 12-15
Power Factor 0.44
Power Loss (W) 16.4
Range DIMENSION
Rated Current (A) 8
Series C series
Special Application Hazardous location, Marine
Standards and Approvals Class I Div. 2 Canada - CSA, Class I Div. 2 USA - CSA, EU Declaration of Conformity, IEC 60950 CB Scheme, Marine ABS, Marine DNV, UL 508 Canada, UL 508 USA, UL 60950-1 Canada, UL 60950-1 USA, UK Declaration of Conformity
Use In Crosslinking Yes
Warranty Period (Months) 36
Weight (g) 500