Specifications

Rated Service Short-Circuit Breaking Capacity Ics at 400 V, 50 Hz 50 kA
Rated Short Circuit Breaking Capacity, (Ics) 690V AC 42 kA
Rated Short Circuit Breaking Capacity, (Icu) 690V AC 42 kA
Rated Ultimate Short Circuit Breaking Capacity (Icu) at 415 V, 50 Hz 50 kA
Product Type Air Circuit Breaker
Brand ABB
Series SACE Emax 2
Application Power Distribution/ Power Control
AC Power Loss Per Pole at In 81.33 W
Air Circuit Breaker (Withdrawable) Withdrawable
Electrical Endurance 6500
Integrated Communication Function Yes
Long Time Overload Protection Adjustment Range 0.4 x In-1 x In
Max. Rated Operation AC Voltage (Ue) 690 VAC
No. of Poles (Total) 3
Rated Current (In) 1250 A
Rated Impulse Withstand Voltage (Uimp) 12 kV
Rated Insulation Voltage (Ui) 1000 V
Short-time Protection Adjustment Range 0.6 x In-10 x In
Short-time Withstand Current (Icw), 1 sec 42 kA
Short-time Withstand Current (Icw), 3 sec 24 kA
Type of Protection Trip Unit Ekip Touch LSI
Frame Size Rating E1.2C
Communication Protocols IEC 61850, Modbus TCP, Modbus RS485, Profibus, Profinet, DeviceNet™, EtherNet/IP™
Power Loss 244 W
Rated Frequency 50Hz60Hz
Trip Curve LSI
Housing Material polyester thermoset
Max. Vibration Accelaration 0.7g
Mechanical Endurance 20000
Depth 271 mm
Height 363.5 mm
Weight 38 kg
Width 278 mm
Rated Surrounding Temperature without Derating 70°C
Pollution Degree Level 3
Operating Temperature 25-+70 °C
IP Rating IP20
Max. Altitude Before Derating 2000 m
Standards and Approvals IEC 609472, EN 60947, CEI EN 60947, IEC 61000, LVD no2014/35EU, EMC no. 2014/30EU, UL 1066, GOST, CCC, UKCA, EN 45011, ACAE