Specifications

Product Type Three-phase monitoring relay
Brand ABB
Series CM-PVS
Function Phase sequence, phase failure, overvoltage and undervoltage monitoring; phase sequence monitoring switchable
Electrical Endurance 100000 cycle
No. of Phases 3
Over Voltage Category III
Rated Control Supply Voltage (Us) 3 x 200 to 400 V AC
Rated Insulation Voltage (Ui) 600 V (input/output); 300 V (between output circuits)
Rated Operational Current AC-15 (Ie) 3 A
Timing Range 200 ms Start-Up Delay, 0.1 to 30 s Tripping Delay
Contact Configuration 2CO SPDT
Measuring Range Overvoltage: 3 x 300 to 400 V AC; undervoltage: 3 x 210 to 300 V AC
Output Type 2CO SPDT
Rated Current 4 A
Rated Frequency 50/60 Hz
Rated Voltage 200-400 VAC
Terminal Type Screw terminals
Rated Operational Current AC-12 (Ie) 4 A
Rated Operational Current DC-12 (Ie) 4 A
Rated Operational Current DC-13 (Ie) 2 A
Time Range Start-up: 200 ms; tripping: 0 s or 0.1 to 30 s
Minimum Switching Capacity 24 V / 10 mA
Rated Operational Voltage (AC/DC) 250 V
Output 2 c/o (SPDT) contacts
Short-Circuit Protective Devices 6 A fast-acting (n/c contact); 10 A fast-acting (n/o contact)
Mechanical Durability 30000000 cycle
Conductor Cross Section Flexible 1 x 0.5 to 2.5 mm²; 2 x 0.5 to 1.5 mm²
Conductor Cross Section Solid Core 1 x 0.5 to 4 mm²; 2 x 0.5 to 2.5 mm²
Housing Material UL 94 V-0
Mounting Type 35 x 15 mm DIN Rail, 35 x 7.5 mm DIN Rail
Depth 103.7 mm
Height 85.6 mm
Weight 0.136 kg
Width 22.5 mm
Pollution Degree 3
Storage Temperature -40 to 85 °C
Operating Temperature -25 to 60 °C
IP Rating IP50 (housing); IP20 (terminals)
Standards and Approvals IEC/EN 60947-5-1; IEC/EN 60255-27; EN 50178; cULus E140448; CCC; CE; UKCA; CMIM
Products to compare: