The ACB E1.2N is a 4P circuit breaker with a rated current (In) of 1600A. It has an Icu rating of 66kA at 415V AC, indicating its ability to interrupt short-circuit currents. The breaker also has a rated short-time withstand current, Icw (1s), of 50kA.
It features a withdrawable auto EKIP touch LSIG trip unit, which provides protection against overload, short circuit, and ground fault conditions. The ACB E1.2N is equipped with shunt opening and closing mechanisms, as well as a motor operator that operates on both 240-250VAC and DC power.
The complete package includes the WMP+FP+YO+YC+MOP components necessary for proper operation.