ABB E2N320WO415K ACB W/Fixed Part 800-2000A 3-P 66kA 380-415VAC Shunt Opening E2.2 Ekip Touch LSIG

Product Code: E2N320WO415K

  • Automatic ACB for 800-2000 A applications
  • Withstands impulse voltage up to 12 kV
  • Ekip Touch LSIG trip unit for precise control
  • Rated short time withstand current of 66 kA
  • Horizontal rear spread terminals
In Stock Low Stock Out Of Stock Please See Attributes

Specifications

Product Type Circuit Breaker
Brand ABB
Breaking Capacity 66 kA
Component Type Withdrawable
Frame Size E2.2
Number of Poles 3
Power Loss 450 W
Rated Current 800-2000 A
Rated Impulse Withstand Voltage 12 kV
Rated Insulation Voltage 1000 VAC
Rated Short Time Withstand Current 66 kA
Rated Voltage 690 VAC
Standards and Approvals IEC 309
Terminal Type Horizontal Rear Spread
Trip Unit Ekip Touch LSIG
Version Withdrawable

Description

When selecting an Automatic Air Circuit Breaker (ACB) for your industrial or commercial application, it’s crucial to consider specifications that align with your operational needs. This ACB is a robust and reliable choice, offering a range of features suited for demanding environments. With a rated current spanning from 800 A to 2000 A, this circuit breaker accommodates varying load requirements effectively. Its rated insulation voltage stands at 1000 VAC, ensuring safe operation under high-voltage conditions. The device also supports a rated voltage of 690 VAC, making it suitable for standard industrial applications. Safety and reliability are paramount in electrical systems, and this ACB doesn't disappoint. It boasts a rated impulse withstand voltage of 12 kV and a short time withstand current capacity of 66 kA. These features provide resilience against transient overvoltages and short-circuit conditions respectively. The Ekip Touch LSIG trip unit integrated into this breaker offers advanced protection functionalities such as long-time (L), short-time (S), instantaneous (I), and ground fault (G) protections. This ensures comprehensive safeguarding against potential electrical faults while maintaining system stability. Power loss is another critical factor in evaluating the efficiency of an electrical device. This model records power loss at 450 W, which is competitive within its category, balancing performance with energy efficiency. Designed with three poles and featuring horizontal rear spread terminals, installation flexibility is enhanced—ideal for various panel configurations without compromising on space or accessibility. This ACB conforms to IEC 309 standards, guaranteeing compliance with international safety regulations—a testament to its quality engineering. In terms of physical dimensions, the frame size E2.2 provides ample room for integration into existing systems without necessitating extensive modifications or upgrades to infrastructure. Overall, this automatic ACB combines durability with precision engineering—a dependable component in any sophisticated electrical setup requiring stringent control measures and reliability under stress conditions.