Products

ABB E4H332WC250K ACB W/Fixed Part 1280-3200A 3-P 100kA 240-250VAC/DC Shunt Closing E4.2 Ekip Touch LSIG

Product Code: E4H332WC250K

  • Automatic ACB with 1280-3200 A rating
  • High breaking capacity of 100 kA
  • Ekip Touch LSIG trip unit for precision
  • Rated voltage up to 690 VAC
  • Complies with IEC 309 standards
In Stock Low Stock Out Of Stock Please See Attributes

Specifications

Size of Frame E4.2
G (0.1 to 1 x In) - I4 (A) 320-3200
I (1.5 to 15 x In) - I3 (A) 4800-48000
L (0.4 to 1 x In) - I1 (A) 1280-3200
No. of Poles 3P
Power Loss (W) 743
Rated Current (A) 3200
Rated Impulse Withstand Voltage (kV) 12
Rated Insulation Voltage AC (V) 1000
Rated Operational Voltage AC (V) 690
Rated Short-time Withstand Current - Icw (kA/1s) 85
Rated Uninterrupted Current - Iu (A) 3200
S (0.6 to 10 x In) - I2 (A) 1920-32000
Breaking Capacity 415V AC - Icu (kA) 100
Poles 3P
Breaking Capacity (kA) 100 @415V AC
Current Rating (A) 3200
Trip Unit - Electronic EKIP Touch LSIG
AC Voltage (V) 690
Frame E4.2
Icw (kA/1s) - Short-time Withstand Current Rating 85
Iu - Uninterrupted Current Rating (A) 3200
Product Type Circuit Breaker
Brand ABB
Breaking Capacity 100 kA
Component Type Withdrawable
Frame Size E4.2
Number of Poles 3
Power Loss 743 W
Rated Current 1280-3200 A
Rated Impulse Withstand Voltage 12 kV
Rated Insulation Voltage 1000 VAC
Rated Short Time Withstand Current 85 kA
Rated Voltage 690 VAC
Standards and Approvals IEC 309
Terminal Type Horizontal Rear Spread
Trip Unit Ekip Touch LSIG
Version Withdrawable

Description

Introducing a robust solution for your industrial and commercial electrical needs, this Automatic Air Circuit Breaker (ACB) is designed to deliver reliable performance in demanding environments. With a rated current range of 1280-3200 A, it provides flexibility and adaptability for various applications. Engineered to meet high safety standards, the breaker boasts a rated impulse withstand voltage of 12 kV and an insulation voltage of 1000 VAC. This ensures that the system can handle significant voltage spikes without compromising on safety or functionality. The breaker is also equipped with an impressive short time withstand current rating of 85 kA, highlighting its ability to endure temporary overcurrent conditions without sustaining damage. The automatic ACB operates at a rated voltage of 690 VAC, suitable for many industrial systems. Its breaking capacity stands strong at 100 kA, offering peace of mind when it comes to interrupting fault currents efficiently. The device features the Ekip Touch LSIG trip unit which enhances protection by providing long-time, short-time, instantaneous, and ground fault protection settings. Power efficiency is crucial in any installation; hence this ACB maintains a power loss figure of just 743 W. Designed with three poles and housed within an E4.2 frame size, it fits seamlessly into existing setups while maintaining optimal performance levels. Installation versatility is ensured with horizontal rear spread terminal types which accommodate various connection configurations easily. Compliance with IEC 309 standards further underlines its reliability and adherence to international safety benchmarks. This automatic circuit breaker offers an excellent balance between technical capability and practical utility—ideal for those seeking dependable circuit protection solutions in their operations.