Products

ABB E6H350WOCM48K ACB W/Fixed Part 2000-5000A 3-P 100kA 48VAC/DC Shunt Open/Close Motor Operator Ekip Touch LSIG

Product Code: E6H350WOCM48K

  • Motor operated ACB for efficient control
  • Handles rated current of 2000-5000 A
  • Rated voltage up to 690 VAC
  • Ekip Touch LSIG trip unit for protection
  • Breaking capacity of 100 kA
In Stock Low Stock Out Of Stock Please See Attributes

Specifications

Size of Frame E6.2
G (0.1 to 1 x In) - I4 (A) 500-5000
I (1.5 to 15 x In) - I3 (A) 7500-75000
L (0.4 to 1 x In) - I1 (A) 2000-5000
No. of Poles 3P
Power Loss (W) 850
Rated Current (A) 5000
Rated Impulse Withstand Voltage (kV) 12
Rated Insulation Voltage AC (V) 1000
Rated Operational Voltage AC (V) 690
Rated Short-time Withstand Current - Icw (kA/1s) 100
Rated Uninterrupted Current - Iu (A) 5000
S (0.6 to 10 x In) - I2 (A) 3000-50000
Breaking Capacity 415V AC - Icu (kA) 100
Poles 3P
Breaking Capacity (kA) 100 @415V AC
Current Rating (A) 5000
Trip Unit - Electronic EKIP Touch LSIG
AC Voltage (V) 690
Frame E6.2
Icw (kA/1s) - Short-time Withstand Current Rating 100
Iu - Uninterrupted Current Rating (A) 5000
Product Type Circuit Breaker
Brand ABB
Breaking Capacity 100 kA
Component Type Withdrawable
Frame Size E6.2
Number of Poles 3
Power Loss 850 W
Rated Current 2000-5000 A
Rated Impulse Withstand Voltage 12 kV
Rated Insulation Voltage 1000 VAC
Rated Short Time Withstand Current 100 kA
Rated Voltage 690 VAC
Standards and Approvals IEC 309
Terminal Type Horizontal Rear Spread
Trip Unit Ekip Touch LSIG
Version Withdrawable

Description

The Motor Operated Air Circuit Breaker (ACB) is a robust and reliable solution designed for industrial and commercial applications, providing optimal protection and control. With a rated current range of 2000 to 5000 A, this ACB caters to diverse power needs, ensuring flexibility in various settings. Engineered with a rated impulse withstand voltage of 12 kV and an insulation voltage of 1000 VAC, the breaker stands strong against electrical surges and ensures safety across operations. The device operates effectively at a rated voltage of 690 VAC, making it suitable for high-demand environments. A key feature is its impressive breaking capacity of 100 kA, which guarantees efficient interruption of fault currents. Coupled with a short-time withstand current rating also at 100 kA, this ACB provides exceptional resilience under extreme conditions. Equipped with the Ekip Touch LSIG trip unit, users benefit from advanced protection features including long-time, short-time, instantaneous, and ground fault protections. This sophisticated unit enhances operational safety by swiftly responding to irregularities. The frame size E6.2 offers compactness without compromising on performance. Designed with three poles and horizontal rear spread terminals, installation is straightforward while maintaining secure connections. Power loss is minimized to just 850 W during operation—an important factor for energy efficiency in large-scale installations. Compliance with IEC 309 standards underscores the product's adherence to international quality benchmarks. In summary, this Motor Operated ACB combines technical excellence with practical functionality to meet demanding electrical distribution requirements reliably.