ABB E6H463WO24K ACB W/Fixed Part 2520-6300A 4-P 100kA 24VAC/DC Shunt Opening E6.2 Ekip Touch LSIG

Product Code: E6H463WO24K

  • Automatic ACB with 2520-6300 A rating
  • Withstands impulse voltage up to 12 kV
  • Rated insulation voltage of 1000 VAC
  • Breaking capacity of 100 kA
  • Ekip Touch LSIG trip unit for control
In Stock Low Stock Out Of Stock Please See Attributes

Specifications

Product Type Circuit Breaker
Brand ABB
Breaking Capacity 100 kA
Component Type Withdrawable
Frame Size E6.2
Number of Poles 4
Power Loss 1550 W
Rated Current 2520-6300 A
Rated Impulse Withstand Voltage 12 kV
Rated Insulation Voltage 1000 VAC
Rated Short Time Withstand Current 100 kA
Rated Voltage 690 VAC
Standards and Approvals IEC 309
Terminal Type Horizontal Rear Spread
Trip Unit Ekip Touch LSIG
Version Withdrawable

Description

When it comes to ensuring the reliability and safety of your electrical systems, selecting the right Automatic Air Circuit Breaker (ACB) is crucial. This particular ACB model offers robust performance and meets high standards, making it a solid choice for industrial and commercial applications. Designed to handle demanding environments, this ACB boasts a rated current range from 2520 A up to 6300 A. Such versatility allows it to cater to various power distribution needs while maintaining efficiency. The breaker is capable of withstanding high impulse voltages, with a rated impulse withstand voltage of 12 kV, assuring resilience against transient overvoltages. Safety and durability are further ensured by its rated insulation voltage of 1000 VAC and an impressive short-time withstand current rating of 100 kA. These specifications highlight its ability to endure extreme conditions without compromising on performance or integrity. Operating at a rated voltage of 690 VAC, this ACB integrates seamlessly into modern electrical networks. It features an advanced Ekip Touch LSIG trip unit that provides precise protection functions including overload (L), short-circuit (S), instantaneous (I), and ground fault (G) protection. This comprehensive protection suite ensures that your system remains secure against various electrical faults. The product's power loss stands at 1550 W, which is within acceptable limits for devices in this category, balancing energy efficiency with operational effectiveness. With four poles available in its configuration, the breaker accommodates multiphase installations efficiently. Breaking capacity is another critical factor where this ACB excels—it can break currents up to 100 kA safely and effectively during fault conditions. The frame size E6.2 indicates a compact yet sturdy design suitable for space-constrained environments while providing ample room for heat dissipation. For ease of installation and maintenance, the terminal type is configured as horizontal rear spread which simplifies connections in switchgear assemblies or panels where space management is essential. Compliance with IEC 309 standards underscores the product's adherence to international quality benchmarks ensuring dependable operation across different regions including Australia’s stringent regulatory landscape. In summary, this Automatic ACB combines flexibility in application with superior safety features tailored for high-demand settings—making it an ideal component in your electrical infrastructure strategy when reliability cannot be compromised.