Specifications

Dimensions (mm) 76.2W x 130H x 70D
No. of Poles 3
Power Loss (W) 3.7
Rated Current (A) 50
Rated Frequency (Hz) 50/60
Rated Insulation Voltage (V) 800
Rated Instantaneous Short-Circuit Current - Ii (A) 500
Rated Uninterrupted Current - Iu (A) 160
Breaking Capacity 415V AC - Icu (kA) 50
I - Short-circuit Current Setting I3 (A) 500
L - Overload Current Setting I1 (A) 35 - 50
Design of Control Element Toggle
EAN 8015644013257
MCCB Type XT1 Frame
Poles 3P
Breaking Capacity (kA) 50
Current Rating (A) 50
Tripping Unit TMD
Voltage (V) 690 AC
Trip Unit - Thermal Magnetic TMD
Main Circuit Electrical Connection Bolt Connection
Main Current Circuit Connection Position Front Side
Rated Voltage (V) 690
Product Type Moulded Case Circuit Breaker
Brand ABB
Breaking Capacity 50 kA
Connection Type Front
Current Setting Range 35-50 A
Degree of Protection IP20
Main Circuit Connecting Capacity 45.5-80 sq-mm
Number of Poles 3
Power Loss 3.7 W
Rated Current 50 A
Rated Frequency 50/60 Hz
Rated Impulse Withstand Voltage 8 kV
Rated Insulation Voltage 800 V
Rated Short Circuit Current 500 A
Rated Voltage 690/500 VAC/VDC
Release Type TM
Standards and Approvals IEC60947-2
Suitable For Use With XT1S
Terminal Type Bolt
Trip Unit TMD
Version Fixed
Weight 1.1 kg
Width 76.2 mm

Description